EA3-022M
Switching actuator without controls and indicators, 22 channels
Last updated
Switching actuator without controls and indicators, 22 channels
Last updated
An overview of the product design and usage. Includes circuit diagrams, terminal details, etc.,
The EA3-022M relay module is designed to provide versatile control capabilities within the iNELS system. Here's an overview of its features:
Relay Outputs: Equipped with 22 relay outputs, including 1x changeover contact suitable for controlling roller blinds or blinds.
Lighting and Socket Circuits:
- Supports switching of lighting and socket circuits using 6 A and 10 A relays.
- Common potential for these circuits is available at the "COMx" terminal, simplifying installation.
Roller Blinds and Blinds Control: Capable of controlling roller blinds and blinds operating within a range of 24 - 230 V AC/DC.
Fan Coil Unit Control:
- Enables relay control of fan coil units for heating/cooling purposes.
- Supports three fan speeds and operates within a range of 24 - 230 V AC/DC.
BUS Connection: Facilitates connection to the iNELS BUS system, enabling communication with the CU3 central unit for centralized control and monitoring.
Modular Design: Designed as a 6-MODULE unit for mounting into a switchboard using DIN rail EN60715, ensuring compatibility with standard installation setups.
The chart illustrates the compatibility between switching actuator and various central units, firmware versions, and integration options.
Introduction
iNELS Design Manager, or IDM3, is for programming iNELS units. This software serves as the platform for configuring device parameters, defining functions, and executing the programming required for iNELS units.
Device parameters, such as sensor range and thresholds, backlights, and operational modes, can be easily adjusted within the IDM3.
The process of programming in IDM3 typically involves defining functions and establishing logical connections between different devices. This allows for the creation of automation scenarios and the implementation of intelligent control strategies.
Starting up
Select the "blue control icon" as shown in Fig 1 > Clicking on the option "New project from default template“ allows you to create a new project from a predefined template.
Select the "Device manager" (Fig 1)> Add "New unit "> Select the central unit > Add "New unit">Select the "Internal-Master/ BUS"> Add "New unit "> Add the devices> Click on the devices to see the "Parameters".
Parameters:
Parameters in the iNELS devices refer to the measurable factors or characteristics that define the behavior or performance of the device. These could include electrical properties, physical dimensions, environmental conditions, and various other specifications depending on the type of device.
These are settings specific to individual devices within your automation system.
The specific parameters of the EA3-022M in the iDM as shown in Fig.2
Clicking on the EA3-022M (Fig.2), we can navigate to firmware, unit address, name, and description, along with other parameters as described below:
It is important to add the device address for proper communication with the unit. The Hexadecimal device address can be find from the device.
Switch limit: The switch limit parameter establishes the highest allowable frequency of relay switching per minute. If the number of switch occurrences surpasses this limit within a minute, the relay will not be triggered.
RE1-RE16 Blocking Group of Parallel Switching: This function is responsible for preventing or halting the simultaneous switching of a relay in parallel with other relays within the designated group. For instance, if you designate RE1, RE2, and RE3 to Blocking group of parallel switching- 1, none of these relays will switch on concurrently. This feature proves useful when connecting these relays to three distinct fans in an air conditioning system. If Fan 1 is activated, Fans 2 and 3 will not switch on in parallel, effectively safeguarding the fans from simultaneous switching.
VALVE 1, 2-OPEN Blocking Group of Parallel Switching: These parameters control the opening of valves 1 and 2. They trigger the simultaneous opening of the specified valves, facilitating fluid flow control within a system.
VALVE 1, 2-CLOSE Blocking Group of Parallel Switching: These parameters control the closing of valves 1 and 2. They trigger the simultaneous closing of the specified valves, halting fluid flow within a system.
RE 1-16: These parameters represent individual relay outputs. They control the switching of various circuits such as lighting, socket circuits, roller blinds, or fan coil units.
Invert Output: This parameter determines whether the output state of the relay is inverted or not. When enabled, it means that the relay output will be active when the control signal is inactive, and vice versa.
Use Default State:In the context of a switching actuator, the term "default state" pertains to the pre-established or initial condition that the actuator adopts in the absence of communication from the bus or central unit. Enabling this function ensures that the relay automatically assumes its default state, which is set to OFF.
Default Output State: Upon choosing the "use default state" option, you will be prompted to specify the default output state. This refers to the pre-established or initial condition that the actuator adopts when there is no communication from the bus stop or central unit. Upon selecting this function, the relay will transition to its default output state, which, in this case, is set to ON.
SHUTTER UP: This parameter controls the upward movement of roller blinds or shutters. It triggers the operation of motors or actuators responsible for raising blinds or shutters.
SHUTTER DOWN: This parameter controls the downward movement of roller blinds or shutters. It triggers the operation of motors or actuators responsible for lowering blinds or shutters.
VALVE 1, 2 OPEN: This parameter controls the opening of valve 1 and valve 2. It triggers the operation of a relay or actuator responsible for opening valve 1 and valve 2, facilitating fluid flow control in a specific application.
VALVE 1, 2 CLOSE: These parameters control the closing of valves 1 and 2. When activated, they trigger the respective valves to close, stopping fluid flow within a system.
ALERT-UNDER-VOLTAGE-RELAY: This parameter indicates an alert related to under-voltage conditions. It signals when the voltage supplied to the relay module falls below a certain threshold, indicating a potential issue with the power supply.
OUF-ALERT-RE1-16: This parameter serves as an indicator for alert conditions associated with relay outputs 1 through 16 on the EA3-022M device. The alert is activated when the switching limit surpasses the configured threshold in any of the relay outputs. Upon activation, this alert signals users about a fault in one of the relay outputs, prompting them to investigate and take corrective measures. This is crucial to prevent potential damage to connected loads or the device itself. The designation "RE1-16" specifies that the alert is applicable to each relay output individually, allowing users to pinpoint the specific relay output affected by the alert.
OUF-ALERT-SHUTTER: This parameter indicates alerts related to the operation of shutters or blinds. It signals an "Over-Current Fault" condition during the operation of the shutter or blind control mechanism.
OUF-ALERT-VALVE1,2-OPEN: These parameters indicate alerts related to the opening of valves 1 and 2. They signal an "Over-Current Fault" condition for the respective valve opening operation.
OUF-ALERT-VALVE1, 2-CLOSE: These parameters indicate alerts related to the closing of valves 1 and 2. They signal an "Over-Current Fault" condition for the respective valve closing operation.
SW (Switch) 1-16: These parameters represent switches for relay outputs 1 through 16. They enable remote or automated control of the relay outputs, allowing for convenient operation from a control system.
SW SHUTTER-UP: This parameter depicts switches for the upward movement of shutters or blinds. It triggers the operation of motors or actuators responsible for raising shutters or blinds.
SW SHUTTER-DOWN: This parameter depicts switches for the downward movement of shutters or blinds. It triggers the operation of motors or actuators responsible for lowering shutters or blinds.
SW VALVE1, 2-OPEN: These parameter depicts switches for the opening of valves 1 and 2. They trigger the operation of relays or actuators responsible for opening the specified valves.
SW VALVE1, 2-CLOSE: These parameters depicts switches for the closing of valves 1 and 2. They trigger the operation of relays or actuators responsible for closing the specified valves.
Setting Up Control and Monitoring for iNELS Cloud and iNELS App
It is possible to control and monitor all the bus units in iNELS cloud and iNELS app. There are two stages to set up this function. Stage one is to do configuration in iDM3 and stage 2 is to do Configuration in iNELS cloud page and iNELS app.
1. Unit and Parameter Selection:
Begin by accessing the iDM3 interface on your PC connected to CU. Navigate to the Device Manager section and carefully select the units and parameters you wish to control. This step is essential for determining what gets exported to the iNELS cloud and app.
2. CU Configuration and Third-Party Settings :
After the above step, go to the CU configuration in the iDM3, and select the page for third-party settings.
Inside the third-party settings page, designate the port for cloud connection. Set the mode of operation and choose the numerical system as hexadecimal. Pay close attention to verifying and configuring all essential parameters for successful cloud export.
3. Cloud Settings:
Move on to the Cloud Settings section within iDM3.
Input the details of your iNELS cloud account. If you haven't created one, utilize the "New User" tab on the iNELS Cloud web page to establish a free account. (Inels Cloud - ElkoEP).
Select the mode and input the cloud account credentials. Save the project to the central unit to generate and store the export project file in the iNELS cloud account.
1. Online Status Verification:
Once the cloud credentials and export settings in iDM3 are configured successfully, check the iNELS cloud account's Gateway section. Confirm that the Central Unit (CU) is online and that the export file has been automatically sent to the cloud under your account.
2. Device Creation in Cloud Platform:
In the cloud platform, you have to create new devices in order to control it remotely.
In the device tab, you will find the add device button, which can be used to associate export elements from IDM with the required types and icons.
After entering any name of the device, you select the icon, the MAC address of the communication gateway (in this case CU3), a specific type of device and the address of a specific function and element from the iNELS BUS system.
In order to be able to use the iNELS application to control the devices from CU over the local network or the cloud, it is necessary to create a room for bus devices for each central unit and add the devices into the room.
Follow these steps meticulously to ensure a seamless configuration process for controlling and monitoring all bus units through iNELS cloud and iNELS app.
iNELS units support MQTT integration on central units CU3-07M, CU3-08M, CU3-09M, and CU3-10M. It is necessary to select the devices and parameters for 3rd party integration on the device manager in the iDM.
Please note that you have an MQTT broker (local or cloud) running in the installation for this integration.
After you have a working MQTT broker you need to configure iNELS Central units to communicate with it. If you have no knowledge of what MQTT is, you can learn about it from MQTT Essentials articles. https://www.hivemq.com/mqtt/
There is a pre-installed MQTT broker in the iNLES bridge, it can be used to connect the iNELS Central units for integration in your projects.
Configuration in iDM3: Select units of 3rd Party integration.
Unit and Parameter Selection:
Begin by accessing the iDM3 interface on your PC connected to CU. Navigate to the Device Manager section and carefully select the units and parameters you wish to control. This step is essential for determining what gets exported to the 3rd party integration via MQTT.
2. CU Configuration and Third-Party Settings :
After the above step, go to the CU configuration in the iDM3, and select the page for third party settings.
Inside the third-party settings page, designate the port for third-party connection. Set the mode of operation and choose the numerical system as hexadecimal. Pay close attention to verifying and configuring all essential parameters for successful third-party integration.
3. MQTT Settings:
Move on to the MQTT Settings section within iDM3.
Input the details of your MQTT broker.
Select the mode and input the broker credentials such as IP, port username and password. Save the project to the central unit.
For MQTT payload description please refer the link below. https://wiki.inels.com/v/inels-bus/3rd-party-integration/mqtt-payload-description-of-inels-bus-devices
Provide any optional, supplementary information that may help in providing a more comprehensive understanding of the product.
SL No | Support Central units | Support FW | Support in MQTT | Support in HASS |
---|---|---|---|---|
1
CU3-01M
02.84.00
NA
NA
2
CU3-02M
02.84.00
NA
NA
3
CU3-07M
02.A0.00
Yes
Yes
4
CU3-08M
02.A0.00
Yes
Yes
6
CU3-09M
Preparation
Preparation
Preparation
7
CU3-10M
Preparation
Preparation
Preparation