Carrier Ducted Split with iNELS CU3-10M/Modbus

1. Introduction

This guide describes how to integrate Carrier ducted split systems (e.g., 38KSM + 42KSM indoor/outdoor units, R-410A) into the iNELS CU3-10M/Modbus controller.

The integration is achieved using the Carrier Translator 33CNTRAN485-01-R, which converts Carrier’s proprietary CCN (Carrier Comfort Network) protocol into Modbus RTU (RS-485), enabling full two-way communication with iNELS.

2. Required Components

  • CU3-10M/Modbus (iNELS Central Unit with Modbus Master support)

  • Optional - Inspinia unit with Addon A-GRS4

  • Carrier ducted split unit (38KSM outdoor + 42KSM indoor or any)

  • Carrier Translator 33CNTRAN485-01-R

  • RS-485 twisted pair cable (shielded, daisy-chain topology)

  • Power supply for translator (24 VAC / 24 VDC depending on model)

3. System Architecture

[CU3-10M/Modbus]  ← RS-485 / Modbus RTU →  [33CNTRAN485-01-R]  ← CCN →  [Carrier Ducted Split Units]
  • CU3-10M or Inspinia unit operates as Modbus Master

  • Translator acts as Modbus Slave / CCN Master

  • Multiple Carrier indoor units can be connected to the translator (check translator capacity in datasheet)

4. Wiring & Connections

  • RS-485 from CU3-10M to Translator (A/B polarity must match).

  • Termination resistors (120 Ω) at both ends of RS-485 bus.

  • Shield grounding at one point only (preferably CU3 side).

  • Translator DIP switch settings → configure for Modbus RTU mode, slave address, and baud rate (default: 9600bps, 8N1).

5. CU3-10M Configuration

In iDM3 (iNELS Design Manager):

  1. Add a Modbus Bus to the CU3-10M device manager.

  2. Create a new device with the translator’s slave address.

  3. Map registers according to Carrier Translator Modbus table (see below).

  4. Assign iNELS objects (bits/integers) for control and monitoring.

6. Modbus Register Mapping (Example)

Function
Register (Hex)
Data Type
Notes

Room Temperature (°C)

30001 (0x0000)

INT16

Scaled ×10

Setpoint Temperature (°C)

40001 (0x0000)

INT16

R/W, scaled ×10

Operating Mode (Cool/Heat/Fan)

40002 (0x0001)

INT16

R/W, enum (0=Auto,1=Cool,2=Heat,3=Fan,4=Dry)

Fan Speed

40003 (0x0002)

INT16

R/W, enum (0=Auto,1=Low,2=Med,3=High)

On/Off Command

40004 (0x0003)

Coil

0=Off, 1=On

Alarm Status

30002 (0x0001)

Coil

1=Fault present

(Registers may vary depending on translator firmware – verify with Carrier Translator manual.)

7. Testing & Commissioning

  1. Power on all devices and confirm translator LED indicates CCN ↔ Modbus communication.

  2. In iDM3, monitor Modbus values (room temp, setpoint, on/off).

  3. Test control functions:

    • Change setpoint from iNELS → confirm update on Carrier unit.

    • Switch modes/fan speeds → confirm indoor unit responds.

    • Turn unit On/Off → verify.

  4. Check alarm register for error conditions.

8. Use Cases

  • Centralized HVAC control from iNELS app or SkyThings.

  • Energy management → automatic shutdown when guest card removed (GRMS).

  • Scenes & automation → e.g., “Welcome scene” activates AC at comfort temperature.

  • Monitoring → room temperature and alarms visible on dashboard.

9. Notes

  • Translator must be ordered separately (Carrier code: 33CNTRAN485-01-R).

  • Default Modbus baud rate: 9600 bps (can be changed).

  • Maximum number of Carrier indoor units per translator: typically 16 (check datasheet).

  • For Modbus TCP integration, an RS-485 → TCP converter is required.

10. References

Last updated