> For the complete documentation index, see [llms.txt](https://wiki.inels.com/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://wiki.inels.com/inels-home/inels-wireless/technical-manual-devices/switch-units/rfsa-61b-rfsa-62b.md).

# RFSA-61B / RFSA-62B

Box-type switch units for mains voltage — RFSA-61B (1 output, 16 A) and RFSA-62B (2 outputs, 8 A each). Wiring, programming card, pairing, clearing, specs.

*Part 3 — Unit reference · Switch units.*

Small radio-controlled switch units that fit into an installation box, a ceiling, or the cover of a lamp or appliance. The **RFSA-61B** switches one load up to 16 A (garage doors and gates included). The **RFSA-62B** switches two separate loads, up to 8 A each. You pair wireless buttons to them with the PROG button on the unit.

{% columns %}
{% column %}
![RFSA-61B](https://2503278529-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FkoLW6hWCvDgagoswDVfD%2Fuploads%2Fsxv6jJLhATrkSCLOjmzh%2Frfsa-61b.png?alt=media)

**RFSA-61B** — 1 output, 16 A, 25 buttons
{% endcolumn %}

{% column %}
![RFSA-62B](https://2503278529-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FkoLW6hWCvDgagoswDVfD%2Fuploads%2FfyV0e12WPIRTVjCOZrNP%2Frfsa-62b.png?alt=media)

**RFSA-62B** — 2 outputs, 8 A each, 12 buttons per output
{% endcolumn %}
{% endcolumns %}

## At a glance

|                       | RFSA-61B               | RFSA-62B                           |
| --------------------- | ---------------------- | ---------------------------------- |
| Outputs               | 1 × switching contact  | 2 × switching contact, independent |
| Load per output       | 16 A / AC1 (4000 VA)   | 8 A / AC1 (2000 VA)                |
| Functions             | 6                      | 6 per output                       |
| Wireless buttons      | up to 25               | up to 12 per output                |
| Range in open space   | up to 200 m            | up to 100 m                        |
| External button input | no                     | no                                 |
| Supply                | 230 V AC, 50–60 Hz     | 230 V AC, 50–60 Hz                 |
| Size / weight         | 49 × 49 × 21 mm / 46 g | 49 × 49 × 21 mm / 46 g             |
| EAN (230 V)           | 8595188136242          | —                                  |

{% hint style="info" %}
The instruction manual (2016) also shows 120 V AC and 12–24 V AC/DC versions of both units. Check the label on your unit for its supply voltage.
{% endhint %}

## Wiring

{% hint style="danger" %}
Switch the circuit off before wiring. Wiring may only be done by a person with the right qualification. The unit is connected with flying leads (CY wire), 90 mm long.
{% endhint %}

**RFSA-61B**

| Lead      | Connect                                                                                                                                      |
| --------- | -------------------------------------------------------------------------------------------------------------------------------------------- |
| N         | Neutral (supply)                                                                                                                             |
| L         | Phase (supply)                                                                                                                               |
| 15 and 18 | The unit's switch contact. Put it in the line to your load: phase to one lead, the load to the other. The load's other wire goes to neutral. |

**RFSA-62B**

| Lead               | Connect                                                         |
| ------------------ | --------------------------------------------------------------- |
| N                  | Neutral (supply)                                                |
| L                  | Phase — supplies the unit and feeds both switch contacts        |
| Output 1, output 2 | One lead per load. The other wire of each load goes to neutral. |

* Mounting: installation box, ceiling, or the cover of a lamp or appliance. Mounting position: any.
* Keep at least 1 cm from other iNELS units. Never mount in a metal box or metal switchboard — it blocks the radio signal.
* For indoor use only.

Wiring diagrams: see page 1 of the instruction manual — [RFSA-61B manual (PDF)](https://www.elkoep.com/media/import/Elko/RFx/RFSA-61B/EN/Manual_RFSA-x1B.pdf), [RFSA-62B manual (PDF)](https://www.elkoep.com/media/import/Elko/RFx/RFSA-62B/EN/Manual_RFSA-62B.pdf).

## Programming card

|                                        | RFSA-61B                                                                                                          | RFSA-62B                                                                                                                     |
| -------------------------------------- | ----------------------------------------------------------------------------------------------------------------- | ---------------------------------------------------------------------------------------------------------------------------- |
| Manual on/off                          | PROG < 1 s                                                                                                        | PROG < 1 s                                                                                                                   |
| Select output                          | —                                                                                                                 | PROG 1–3 s — the LED shows the selected output (see hint below)                                                              |
| **Enter programming**                  | **Hold PROG until the LED flashes once per second**                                                               | **PROG 3–5 s**                                                                                                               |
| Finish programming                     | PROG < 1 s                                                                                                        | PROG < 1 s                                                                                                                   |
| Timing mode (5× / 6×)                  | PROG more than 5 s                                                                                                | PROG more than 5 s                                                                                                           |
| **Clear one button**                   | **PROG 5 s**                                                                                                      | **PROG 8 s**                                                                                                                 |
| **Clear whole memory (factory reset)** | **PROG 8 s**                                                                                                      | **PROG 11 s**                                                                                                                |
| Functions                              | [1×–6×](https://wiki.inels.com/inels-home/inels-wireless/appendices/appendix-b-functions-by-number-of-presses.md) | [1×–6×](https://wiki.inels.com/inels-home/inels-wireless/appendices/appendix-b-functions-by-number-of-presses.md) per output |
| Buttons                                | up to 25                                                                                                          | up to 12 per output                                                                                                          |
| Pairs with                             | All iNELS RF Control and RF Control2 controllers and system units; RFIO2 detectors                                | same                                                                                                                         |

{% hint style="info" %}
**RFSA-62B — selecting the output.** The LED flashes in a different colour for each output. See the [RFSA-62B instruction manual (PDF)](https://www.elkoep.com/media/import/Elko/RFx/RFSA-62B/EN/Manual_RFSA-62B.pdf) for which colour belongs to which output, and check after pairing that the button switches the output you wanted.
{% endhint %}

## Pair a controller button

{% stepper %}
{% step %}

### Controller into pairing mode

Hold the controller's pairing button 1 s (red LED short blink). Older controllers: [Pairing reference](https://wiki.inels.com/inels-home/inels-wireless/pairing-and-configuration.md).
{% endstep %}

{% step %}

### RFSA-62B only: choose the output

Hold PROG **1–3 s** and release. The LED flashes in the colour of the selected output (see the hint above). Repeat to switch to the other output.
{% endstep %}

{% step %}

### Unit into programming mode

RFSA-61B: hold PROG until the LED flashes once per second. RFSA-62B: hold PROG **3–5 s**; the LED then flashes once per second.
{% endstep %}

{% step %}

### Choose the function

Press the controller button **1–6 times, about 1 s apart** ([Appendix B](https://wiki.inels.com/inels-home/inels-wireless/appendices/appendix-b-functions-by-number-of-presses.md)). The LED lights at each press, so you can see the unit received it.
{% endstep %}

{% step %}

### Finish

Short press PROG (< 1 s). The LED shows the memory-function setting and the unit returns to operation.
{% endstep %}
{% endstepper %}

| Presses | Function                                                         |
| ------- | ---------------------------------------------------------------- |
| 1×      | Button — on while pressed, off when released (hold at least 1 s) |
| 2×      | Switch on                                                        |
| 3×      | Switch off                                                       |
| 4×      | Impulse relay — every press flips the output                     |
| 5×      | Delayed off — on when pressed, off after the set time            |
| 6×      | Delayed on — off when pressed, on after the set time             |

### Delayed off / delayed on (5× / 6×)

After the 5 or 6 presses, hold PROG **more than 5 s** (LED flashes twice per second). Timing starts when you release. When the time you want has passed (2 s – 60 min), press the same controller button once to store it, then short press PROG to finish.

To pair a wall-switch or other button that already works with this unit, see [How programming works](https://wiki.inels.com/inels-home/inels-wireless/how-programming-works.md). These units have no input for a wired button.

## Memory function

Decides what the output does after a power cut.

1. Put the unit into programming mode (as above).
2. Short press PROG (< 1 s). This **reverses** the memory setting and leaves programming mode.
3. The LED shows the new setting: **3 blinks = on**, **one long light = off**.

| Setting            | After a power cut                                               |
| ------------------ | --------------------------------------------------------------- |
| On — functions 1–4 | Output returns to its last state (saved 15 s after each change) |
| On — functions 5–6 | Output goes to the state it would have at the end of the delay  |
| Off                | Output stays off                                                |

## Clear and factory reset

**One button.** Hold PROG **5 s** (RFSA-62B: **8 s**) — LED flashes 4× per second. Press the controller button to remove. One long flash confirms.

**Whole memory = factory reset.** Hold PROG **8 s** (RFSA-62B: **11 s**) — LED flashes 4× per second. All buttons are removed; the unit stays in programming mode (LED every 0.5 s, up to 4 min). Short press PROG (< 1 s) to leave.

Clearing does not change the memory-function setting.

## Use with eLAN-204 and service tools

* The **address printed on the front** of the unit (one per output on the RFSA-62B) is used to program it from system units and to add it to a gateway.
* To add it to an [eLAN-204](https://wiki.inels.com/inels-home/inels-wireless/technical-manual-devices/system-units/elan-204.md) gateway: open the Devices tab, press **ADD device**, choose the model from the list, enter the RF address shown on the unit, then choose an icon and a name ([Web interface tabs](https://wiki.inels.com/inels-home/inels-wireless/technical-manual-devices/system-units/elan-204/web-interface-tabs-description.md)). Add each output of the RFSA-62B separately.
* The **repeater function** can be switched on with the RFAF/USB service device (units marked RF Control2 / RFIO2).

## LED reference

| LED                             | Meaning                                                |
| ------------------------------- | ------------------------------------------------------ |
| Flashes once per second         | Programming mode                                       |
| Lights at each controller press | Command received (in programming and clearing mode)    |
| Flashes twice per second        | Timing mode                                            |
| Flashes 4× per second           | Clear mode                                             |
| Flashes every 0.5 s             | Memory cleared, waiting in programming mode            |
| 3 blinks / one long light       | Memory function on / off                               |
| Red / green (RFSA-62B)          | Selected output — see the hint in the programming card |

## Troubleshooting

| Symptom                                             | Fix                                                                                                                                                                                                                                |
| --------------------------------------------------- | ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Unit flashes 4× per second when you try to pair     | PROG held too long (that is clear mode). Release, wait, hold again for the right time                                                                                                                                              |
| Function is wrong                                   | Presses were less than 1 s apart or the count was off. Repeat pairing; one press every second                                                                                                                                      |
| RFSA-62B button controls the wrong output           | Select the output (PROG 1–3 s) before entering programming                                                                                                                                                                         |
| Works close by, not in place                        | Range — see [How programming works](https://wiki.inels.com/inels-home/inels-wireless/how-programming-works.md). Metal boxes and switchboards block the signal. Use an RFRP-20 repeater or an RFIO2 unit with the repeater function |
| Light comes on / does not come on after a power cut | Change the memory function                                                                                                                                                                                                         |

## Technical parameters

|                                   | RFSA-61B                                       | RFSA-62B                                     |
| --------------------------------- | ---------------------------------------------- | -------------------------------------------- |
| Supply                            | 230 V AC, 50–60 Hz, +10 % / −15 %              | 230 V AC, 50–60 Hz, +10 % / −15 %            |
| Apparent input / dissipated power | 7 VA (cos φ = 0.1) / 0.7 W                     | 7 VA (cos φ = 0.1) / 0.7 W                   |
| Output                            | 1 × switching, AgSnO₂                          | 2 × switching, AgSnO₂                        |
| Rated current / switching power   | 16 A / AC1, 4000 VA / AC1, 384 W / DC          | 8 A / AC1, 2000 VA / AC1 (per output)        |
| Peak current                      | 30 A / < 3 s                                   | 10 A / < 3 s                                 |
| Switching voltage                 | 250 V AC1 / 24 V DC                            | 250 V AC1                                    |
| Min. DC switching power           | 500 mW                                         | 500 mW                                       |
| Service life                      | mechanical 3 × 10⁷, electrical (AC1) 0.7 × 10⁵ | mechanical 1 × 10⁷, electrical (AC1) 1 × 10⁵ |
| Protocol / frequency              | RFIO2, bidirectional, 866–922 MHz              | RFIO2, bidirectional, 866–922 MHz            |
| Repeater function                 | yes                                            | yes                                          |
| Range                             | up to 200 m in open space                      | up to 100 m in open space                    |
| Operating temperature             | −15 to +50 °C                                  | −15 to +50 °C                                |
| Protection                        | IP30                                           | IP30                                         |
| Overvoltage category / pollution  | III / 2                                        | III / 2                                      |
| Leads (CY wire)                   | 2 × 0.75 mm², 2 × 2.5 mm², 90 mm long          | 0.75 mm² and 2.5 mm² leads, 90 mm long       |
| Dimensions / weight               | 49 × 49 × 21 mm / 46 g                         | 49 × 49 × 21 mm / 46 g                       |
| Standards                         | EN 60730, EN 63044, EN 300 220, EN 301 489     | EN 60669, EN 300 220, EN 301 489             |

Load capacity for other load types: see the catalog *Product loadability* table (16 A AgSnO₂ contacts for the RFSA-61B, 8 A for the RFSA-62B).

## Downloads

* [Instruction manual RFSA-11B / RFSA-61B (PDF)](https://www.elkoep.com/media/import/Elko/RFx/RFSA-61B/EN/Manual_RFSA-x1B.pdf)