DALI

Part 3 — Reference.

Managers ribbon tab → Dali manager


21.1 Two ways to do DALI — pick the right one first

DALI is a lighting bus in its own right. iNELS3 reaches it two different ways, and they are not interchangeable. Choosing the wrong one wastes a day on site.

CU3-09M

RC3-610M/DALI

What it is

A central unit with a built-in DALI master

A room controller with DALI outputs

Addressing the ballasts

In iDM3, using the Dali manager

Externally, with a DALI commissioning tool

Ballast parameters

Read and written from the Dali manager

Set externally, before you touch iDM3

What you do in iDM3

Commission the whole bus

Type in the address each ballast already has

Covered in

§21.2 – §21.6

§21.7

The Dali manager works only with a CU3-09M. It is the only central unit with a DALI master, and the manager talks to that master. If the site has any other CU, the Dali manager is not the route — and the DALI addressing has to happen outside iDM3 entirely.

Establish which hardware is on site before you quote the job. "We'll do the DALI in iDM3" is only true on a CU3-09M. With an RC3-610M/DALI you need a DALI commissioning tool and someone who knows how to use it — a different skill and a different day's work.

The CU3-09M's DALI bus needs its own power supply. DALI is not powered by the iNELS BUS. Budget for a DALI bus power supply or the ballasts will not respond at all.

DALI addresses run 0x00 to 0x3F (0 to 63) — 64 ballasts per bus.


21.2 CU3-09M — getting to the Dali manager

  1. Project ribbon tab → Device manager.

  2. Select the central unitNew slaveInternal-DALI-MasterOK. This is the CU3-09M's own DALI bus. It has no parameters of its own.

  3. Close the Device manager and save.

  4. Managers ribbon tab → Dali manager.

  5. Select the DALI master — double-click it, or highlight it and click ✓ OK.

You are now talking to the DALI bus live, so the central unit must be connected (Chapter 23). The Dali manager reads from and writes to real ballasts; it is not an offline editor.


21.3 The toolbar

Button
What it does

Master

Switch between ballasts and masters (e.g. DALI sensors such as DLS3-1 or DMD3-1)

Add new

Address only new ballasts, leaving existing addresses alone

Search

Read the current ballast addresses from the bus

New DALI

Delete all addresses and reassign from scratch

Change address

Apply the address you typed to the selected ballast

Delete address

Remove a duplicate address

TEST

Blink the output 0 % → 100 % for one second

MIN

Set the output to its configured minimum

MAX

Set it to its configured maximum

OFF

Switch it off

Read params

Load the ballast's current parameters, groups and state

Write params

Apply your changes to the ballast

While working, the buttons show progress states — Changing address, Deleting address, Reading params, Writing params.

TEST, MIN, MAX and OFF all work on a single ballast, a ballast group, or every ballast on the DALI bus.

Use "New DALI" only on a first commissioning. It deletes every address and reassigns them in random order. On an already-configured system that means every ballast in the building swaps identity with another, and every wire you have drawn now controls the wrong light. To add ballasts to a working system, use Add new.


21.4 Addressing

New ballasts ship without addresses, so a Search on a fresh installation shows nothing on the left — that is expected, not a fault.

The typical first commissioning:

  1. New DALI — assigns addresses to everything.

  2. Search — read back what was assigned.

  3. Work through the ballasts using TEST to identify which light is which physically.

  4. Select a ballast, click its address field, type the last digits of the address you want, and click Change address.

  5. Search again to confirm.

The address field shows DALI 0x00 style hexadecimal, editable by clicking it with the left mouse button. Valid range 0x00–0x3F.

Duplicate addresses are flagged with a red exclamation mark in the list on the left. The Dali manager will not write a duplicate, but one can arrive from an existing installation. Clear it with Delete address, then reassign.


21.5 Ballast parameters

Select a ballast to see its Parameters, Groups, Scenes and Status.

Parameters

Field
Meaning

Act. level

Current output level

Power on level

Level adopted when power is applied

System fail level

Level adopted when the DALI bus fails

Min / Max

Configured dimming limits

Phys. min

The ballast's physical minimum — a hardware property

Fade time

Time for a commanded level change

Fade rate

Rate of continuous dimming

System fail level is worth setting deliberately: it decides whether a room goes dark or goes to full when the DALI bus drops.

Status

Indicator
Meaning

Status of ballast

Overall state

Lamp failure

The lamp has failed

Lamp arc. power ON

The lamp is lit

Limit error

A commanded level fell outside Min/Max

Fade ready

A fade has completed

Reset state

The ballast is in its reset state

Miss short addr.

The ballast has no short address

Power failure

Power was lost

Lamp failure is the useful one on a live site — it tells you which fitting has failed without walking the building.

Groups and Scenes

DALI has its own group and scene concept, held in the ballasts themselves — separate from iNELS3 groups.

Use
When

DALI groups and scenes

Everything is DALI, and you want the ballasts to respond together on the DALI bus

iNELS3 groups

The group mixes DALI with relays or other iNELS outputs

Assignments are written to the ballast with Write params, then verified with Read params.


21.6 RC3-610M/DALI — externally addressed

Everything above needs a CU3-09M. The RC3-610M/DALI works differently, and the difference is fundamental: iDM3 does not address these ballasts and does not configure them.

The RC3-610M/DALI is a room controller with relay outputs, inputs, temperature sensors and 16 DALI output channels. The Dali manager cannot see them — there is no DALI master for it to talk to. So the commissioning happens outside iDM3, and iDM3 is only told the result.

The order of work

Step 1 is not an iDM3 task at all. You need a DALI commissioning tool — a handheld programmer or a PC interface with DALI software — to give each ballast a short address (0–63) and set its levels and fade times. If that has not been done, there is nothing for iDM3 to point at.

Get the addressing done before you arrive to program. On an RC3-610M site, the DALI work and the iNELS work are two separate jobs. If the electrician has not addressed the ballasts, you cannot proceed — and no amount of iDM3 configuration will help.

Step 2 — Record the addresses

Whoever addresses the ballasts must hand over a list:

DALI address
Fixture
Room

0

Downlight 1

Living room

1

Downlight 2

Living room

2

Pendant

Kitchen

Without this you are guessing, and the only way to recover it is to walk the building switching addresses on and off one at a time.

Step 3 — Add the unit in iDM3

  1. ProjectDevice manager.

  2. Select the bus master under the CU → New unitRC3-610M-DALIOK.

  3. Set the unit's Address and Description as for any other unit (Chapter 16).

The unit carries 48 device slots in total — its relays, inputs, temperature sensors and the 16 DALI output channels.

Step 4 — Enter each DALI address

Expand the unit, select a DALI output device, and set its parameters:

Parameter
What to enter

DALI address.

The short address that fixture already has, from your list

Use default state:

Whether the output falls back to a set level if communication is lost

Default output state:

The level it falls back to, when the above is enabled

Repeat for each of the 16 channels you are using, and describe each one — Living room downlight 1 — so the names mean something later.

This is the whole of DALI configuration in iDM3 for an RC3-610M. There is no search, no addressing, no parameter read/write, no test button. You are telling iDM3 which address to send commands to, nothing more.

Set "Use default state" on anything that matters. If the DALI link drops, an output with no default simply holds its last value. On escape routes or a reception area, define what it should do instead.

Step 5 — Wire it

From here it is ordinary dimming. Each DALI output is an analog consumer, so everything from Tutorial 3 applies unchanged — ANALOG_SET_LEVEL_50, ANALOG_LEVEL_UP with ANALOG_STOP_LEVEL_CHANGE on Long up, ramps, groups.

Put the DALI outputs in an Analog group (Tutorial 4) and one button dims the whole room.

If a light does not respond

Check

Was the ballast ever addressed?

It needs a short address from a commissioning tool

Does DALI address. match the list?

The commonest error — a transposed digit

Two fixtures respond together

Duplicate addresses — re-address externally

Nothing on the whole channel

DALI bus power supply, or the wiring to that channel

Wrong fixture responds

The handover list is wrong — re-verify address by address

Note that none of these are fixable in iDM3 except a mistyped address. The rest are DALI-side problems needing the commissioning tool.


21.7 Practical advice

Both routes:

Address before you program

Wires point at addresses; changing them afterwards breaks everything

Record the final address list

You will need it the next time somebody changes a fitting

Provide DALI bus power

DALI is not powered from the iNELS BUS

CU3-09M only:

Use TEST to map lights to addresses

Guessing from a drawing is how installations end up mislabelled

Never run New DALI on a live system

It reshuffles every address

Always Read params after Write params

It is the only confirmation you get

RC3-610M/DALI only:

Confirm the ballasts are addressed before your visit

Nothing can be done in iDM3 until they are

Get the address list in writing

Recovering it means walking the building fixture by fixture

Set a default output state

An unaddressed fallback holds the last value when the link drops


Next: Chapter 22 — Central unit configuration.