> For the complete documentation index, see [llms.txt](https://wiki.inels.com/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://wiki.inels.com/inels-bus/inels-design-manager-idm3/common-idm3-support-questions.md).

# Common questions — support index

*Support index — a symptom or question, and the chapter that answers it.*

***

This page exists to get you from a customer's words to the right chapter fast. It is phrased the way people actually ask, not the way the manual is organised.

***

## "It doesn't work"

| The customer says                        | Likely cause                                          | Chapter                                                                                                                                                       |
| ---------------------------------------- | ----------------------------------------------------- | ------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| The button does nothing at all           | Icon not assigned — yellow dot on the floor plan      | [30 §30.1](/inels-bus/inels-design-manager-idm3/troubleshooting-idm3.md) · [17 §17.4](/inels-bus/inels-design-manager-idm3/idm3-floors-and-the-design-tab.md) |
| I uploaded but nothing changed           | Saved the file but never did **Save to central unit** | [23](/inels-bus/inels-design-manager-idm3/connecting-and-uploading-to-the-central-unit.md)                                                                    |
| It worked before, now it doesn't         | The CU is running a different project                 | [23 §23.6](/inels-bus/inels-design-manager-idm3/connecting-and-uploading-to-the-central-unit.md)                                                              |
| Some devices are missing / disconnected  | Addresses don't match the hardware                    | [16](/inels-bus/inels-design-manager-idm3/idm3-device-manager-reference.md)                                                                                   |
| The relay clicks but the light stays off | The project is right — the fault is electrical        | [26 §26.5](/inels-bus/inels-design-manager-idm3/idm3-simulation-and-monitor.md)                                                                               |
| Nothing responds after a power cut       | Non-volatile not set; no `System start` wire          | [12 §12.4](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md)                                                                   |

## Lights and switching

| The customer says                                 | Answer                                                          | Chapter                                                                                     |
| ------------------------------------------------- | --------------------------------------------------------------- | ------------------------------------------------------------------------------------------- |
| The button only turns the light on, never off     | `Digital switch ON` isn't a toggle — use `DIGITAL_SWITCH`       | [6 §1](/inels-bus/inels-design-manager-idm3/tutorial-toggles-impulses-and-delays.md)        |
| I want a staircase light that switches itself off | Impulse function with an impulse time                           | [6 §2](/inels-bus/inels-design-manager-idm3/tutorial-toggles-impulses-and-delays.md)        |
| Pressing again doesn't restart the timer          | `Digital_Impulse_ON` ignores an output already on — use a timer | [12 §12.2](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md) |
| I want one button to do two things                | Two actions on one wire — `Short down` and `Long down`          | [6 §4](/inels-bus/inels-design-manager-idm3/tutorial-toggles-impulses-and-delays.md)        |
| I want a delay before it switches off             | `Digital delay switch OFF`                                      | [6 §5](/inels-bus/inels-design-manager-idm3/tutorial-toggles-impulses-and-delays.md)        |
| How do I switch everything off from one button    | A group                                                         | [8](/inels-bus/inels-design-manager-idm3/tutorial-groups-and-scenes.md)                     |

## Dimming

| The customer says                         | Answer                                                               | Chapter                                                                                     |
| ----------------------------------------- | -------------------------------------------------------------------- | ------------------------------------------------------------------------------------------- |
| The light runs to 100% after I let go     | Missing `Analog stop changing level` on `Long up`                    | [7 §3](/inels-bus/inels-design-manager-idm3/tutorial-dimming-with-analog-functions.md)      |
| Holding the button doesn't dim            | Needs `Analog increasing level` on `Long down`                       | [7 §3](/inels-bus/inels-design-manager-idm3/tutorial-dimming-with-analog-functions.md)      |
| The dimmer forgets its brightness         | `Analog switch value` only moves 0%↔100% — needs a system integer    | [12 §12.5](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md) |
| My 10-second ramp only takes 2 seconds    | Ramp length is the **0→100%** time; partial changes are proportional | [7 §5](/inels-bus/inels-design-manager-idm3/tutorial-dimming-with-analog-functions.md)      |
| I want the light to fade, not jump        | `Analog set level w ramp`                                            | [7 §5](/inels-bus/inels-design-manager-idm3/tutorial-dimming-with-analog-functions.md)      |
| I want a specific brightness on one press | `ANALOG_SET_LEVEL_25/50/75`                                          | [7 §4](/inels-bus/inels-design-manager-idm3/tutorial-dimming-with-analog-functions.md)      |

## Blinds and shutters

| The customer says                       | Answer                                                               | Chapter                                                                                 |
| --------------------------------------- | -------------------------------------------------------------------- | --------------------------------------------------------------------------------------- |
| How do I control blinds                 | Digital impulse — short time tilts, long time runs full travel       | [9](/inels-bus/inels-design-manager-idm3/tutorial-blinds-and-shutters.md)               |
| The blind won't stop when I press again | `Digital_Impulse_ON` ignores an active output — add an explicit stop | [9 §4](/inels-bus/inels-design-manager-idm3/tutorial-blinds-and-shutters.md)            |
| The blind doesn't reach the end         | Impulse time shorter than real travel time                           | [9 §5](/inels-bus/inels-design-manager-idm3/tutorial-blinds-and-shutters.md)            |
| The slats tilt too far                  | Reduce the tilt impulse time                                         | [9 §5](/inels-bus/inels-design-manager-idm3/tutorial-blinds-and-shutters.md)            |
| Can blinds close at sunset              | Astronomical module                                                  | [11 §11.2](/inels-bus/inels-design-manager-idm3/tutorial-time-control-and-schedules.md) |

## Heating and cooling

| The customer says                        | Answer                                     | Chapter                                                                           |
| ---------------------------------------- | ------------------------------------------ | --------------------------------------------------------------------------------- |
| Heating doesn't come on                  | Check **Monitor → Heat/Cool areas** first  | [30 §30.8](/inels-bus/inels-design-manager-idm3/troubleshooting-idm3.md)          |
| The temperature is wrong                 | The time plan, or which plan the area uses | [20 §20.6](/inels-bus/inels-design-manager-idm3/idm3-system-manager-reference.md) |
| How do I set a heating schedule          | Time plan, then Heat/Cool area             | [10](/inels-bus/inels-design-manager-idm3/tutorial-heating-and-cooling.md)        |
| Heating and cooling run at the same time | **Check the difference between…** → `On`   | [20 §20.7](/inels-bus/inels-design-manager-idm3/idm3-system-manager-reference.md) |
| One room never heats                     | That room's **Heating output**             | [20 §20.7](/inels-bus/inels-design-manager-idm3/idm3-system-manager-reference.md) |
| No room heats                            | The shared **Heating supply**              | [20 §20.7](/inels-bus/inels-design-manager-idm3/idm3-system-manager-reference.md) |
| How do I protect against freezing        | **Antifreeze temperature** on every area   | [10 §10.4](/inels-bus/inels-design-manager-idm3/tutorial-heating-and-cooling.md)  |
| What are Favorite1–4                     | The four preset temperatures               | [10 §10.3](/inels-bus/inels-design-manager-idm3/tutorial-heating-and-cooling.md)  |
| Holiday mode for heating                 | Holiday plan + a continuous program        | [10 §10.6](/inels-bus/inels-design-manager-idm3/tutorial-heating-and-cooling.md)  |

## Timers, counters, logic

| The customer says                         | Answer                                           | Chapter                                                                                     |
| ----------------------------------------- | ------------------------------------------------ | ------------------------------------------------------------------------------------------- |
| Corridor light should restart on movement | A timer — `Timer start` restarts a running timer | [12 §12.2](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md) |
| I want to count something                 | A counter                                        | [12 §12.3](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md) |
| How do I remember a state                 | A system bit, **non volatile**                   | [12 §12.4](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md) |
| Holiday mode is lost after a reboot       | **non volatile** wasn't ticked                   | [12 §12.4](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md) |
| Only do this if it's dark / cold / off    | A condition                                      | [12 §12.6](/inels-bus/inels-design-manager-idm3/tutorial-timers-counters-and-conditions.md) |
| What do system bits and integers do       | Storage the whole project can read and write     | [20 §20.4](/inels-bus/inels-design-manager-idm3/idm3-system-manager-reference.md)           |

## Schedules and time

| The customer says               | Answer                                   | Chapter                                                                                 |
| ------------------------------- | ---------------------------------------- | --------------------------------------------------------------------------------------- |
| Do something at a set time      | A **Periodical** program                 | [11 §11.3](/inels-bus/inels-design-manager-idm3/tutorial-time-control-and-schedules.md) |
| On for part of the week         | A **Two-state** program                  | [11 §11.4](/inels-bus/inels-design-manager-idm3/tutorial-time-control-and-schedules.md) |
| Between two dates               | A **Continuous** program                 | [11 §11.5](/inels-bus/inels-design-manager-idm3/tutorial-time-control-and-schedules.md) |
| I can't save my program         | No day or month ticked                   | [11 §11.3](/inels-bus/inels-design-manager-idm3/tutorial-time-control-and-schedules.md) |
| Sunset switching is an hour out | The CU's **Time zone**                   | [22 §22.2](/inels-bus/inels-design-manager-idm3/idm3-central-unit-configuration.md)     |
| Lights on at dusk all year      | Astronomical module with a sunset offset | [11 §11.2](/inels-bus/inels-design-manager-idm3/tutorial-time-control-and-schedules.md) |

## Connection and upload

| The customer says                   | Answer                       | Chapter                                                                                          |
| ----------------------------------- | ---------------------------- | ------------------------------------------------------------------------------------------------ |
| I can't connect to the central unit | **Ping test** first          | [23 §23.2](/inels-bus/inels-design-manager-idm3/connecting-and-uploading-to-the-central-unit.md) |
| It says BadPassword                 | Wrong CU password            | [23 §23.3](/inels-bus/inels-design-manager-idm3/connecting-and-uploading-to-the-central-unit.md) |
| It says UpdateRequired              | CU firmware too old          | [25](/inels-bus/inels-design-manager-idm3/idm3-firmware-update-manager.md)                       |
| Compile error                       | Click the button and read it | [30 §30.3](/inels-bus/inels-design-manager-idm3/troubleshooting-idm3.md)                         |
| I lost the project file             | **Load from central unit**   | [15 §15.6](/inels-bus/inels-design-manager-idm3/idm3-projects-and-files.md)                      |
| How do I change the CU's IP address | **CU configuration**         | [22 §22.2](/inels-bus/inels-design-manager-idm3/idm3-central-unit-configuration.md)              |

## Groups, scenes and reuse

| The customer says                          | Answer                                                    | Chapter                                                                                       |
| ------------------------------------------ | --------------------------------------------------------- | --------------------------------------------------------------------------------------------- |
| A light won't join my group                | Wrong group type — relays and dimmers can't share one     | [8 §The four group types](/inels-bus/inels-design-manager-idm3/tutorial-groups-and-scenes.md) |
| How do I build a scene                     | Separate wires with different levels, not a group         | [8 §5](/inels-bus/inels-design-manager-idm3/tutorial-groups-and-scenes.md)                    |
| The group function names look wrong        | Untranslated in 3.5.3 — `GroupDigital_SwitchOn` is normal | [8](/inels-bus/inels-design-manager-idm3/tutorial-groups-and-scenes.md)                       |
| I keep building the same thing             | Macros, or function blocks                                | [14](/inels-bus/inels-design-manager-idm3/tutorial-macros-and-function-blocks.md)             |
| My macro didn't apply                      | Its **Type** doesn't match the actor type                 | [14 §14.2](/inels-bus/inels-design-manager-idm3/tutorial-macros-and-function-blocks.md)       |
| Editing the macro changed nothing          | Macros are copied into wires, not linked                  | [14 §14.2](/inels-bus/inels-design-manager-idm3/tutorial-macros-and-function-blocks.md)       |
| A function block does nothing              | Inputs/outputs not plugged in, or **Connect** not pressed | [14 §14.3](/inels-bus/inels-design-manager-idm3/tutorial-macros-and-function-blocks.md)       |
| A colleague can't open my project properly | Function block templates live outside the `.elp`          | [14 §14.3](/inels-bus/inels-design-manager-idm3/tutorial-macros-and-function-blocks.md)       |

## Hotel installations

| The customer says                               | Answer                                                 | Chapter                                                               |
| ----------------------------------------------- | ------------------------------------------------------ | --------------------------------------------------------------------- |
| Rooms don't show up in iNELS Harmony            | No Hotel-Room object — Harmony discovers rooms from it | [34 §34.1](/inels-bus/inels-design-manager-idm3/hotel-room-object.md) |
| What is the Hotel-Room object for               | One object per guest room: status, climate, scenes     | [34 §34.1](/inels-bus/inels-design-manager-idm3/hotel-room-object.md) |
| Where do I enter the room number                | **Room-Id** on the Hotel-Room unit — not the Address   | [34 §34.3](/inels-bus/inels-design-manager-idm3/hotel-room-object.md) |
| Guest can set a temperature but nothing happens | Heat/Cool area outputs never wired to hardware         | [34 §34.5](/inels-bus/inels-design-manager-idm3/hotel-room-object.md) |
| How does the PMS read a room                    | One MQTT topic pair per room                           | [34 §34.8](/inels-bus/inels-design-manager-idm3/hotel-room-object.md) |
| DND light doesn't match the button              | Drive the backlight from the DND datapoint             | [34 §34.6](/inels-bus/inels-design-manager-idm3/hotel-room-object.md) |
| Empty rooms stay warm                           | Wire Occupancy off → setback                           | [34 §34.7](/inels-bus/inels-design-manager-idm3/hotel-room-object.md) |

## Integration

| The customer says                         | Answer                                         | Chapter                                                                                             |
| ----------------------------------------- | ---------------------------------------------- | --------------------------------------------------------------------------------------------------- |
| Can I use it with Home Assistant          | MQTT                                           | [24 §24.4](/inels-bus/inels-design-manager-idm3/idm3-external-systems-mqtt-modbus-cloud.md)         |
| MQTT isn't working                        | Needs CU firmware `02.97.02` or later          | [24 §24.4](/inels-bus/inels-design-manager-idm3/idm3-external-systems-mqtt-modbus-cloud.md)         |
| Can I read an energy meter                | Modbus master                                  | [32 §32.5](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| Can a BMS read the installation           | Modbus slave                                   | [32 §32.7](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| Does it do Modbus RTU or just TCP         | Both — but **RTU needs a CU3-10M**             | [32 §32.3](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| Internal-Modbus-Master isn't in the list  | The CU isn't a CU3-10M                         | [32 §32.3](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| RTU meter, but the site has a CU3-08M     | Gateway, CU swap, or GRT3-100 master           | [32 §32.3](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| Which CU do I need for Modbus             | IP: any. RTU: CU3-10M only.                    | [32 §32.3](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| Can two central units talk to each other  | Yes — Modbus IP                                | [33](/inels-bus/inels-design-manager-idm3/linking-two-inels-central-units-over-modbus-ip.md)        |
| Button on one CU, light on another        | Link them over Modbus IP                       | [33](/inels-bus/inels-design-manager-idm3/linking-two-inels-central-units-over-modbus-ip.md)        |
| CU link worked, then stopped              | The slave CU's IP changed — DHCP               | [33 §33.8](/inels-bus/inels-design-manager-idm3/linking-two-inels-central-units-over-modbus-ip.md)  |
| Value moves on one CU, not the other      | Register address, data type or scaling differs | [33 §33.8](/inels-bus/inels-design-manager-idm3/linking-two-inels-central-units-over-modbus-ip.md)  |
| How do I share a temperature between CUs  | One register, `Multiplication 10x` both sides  | [33 §33.10](/inels-bus/inels-design-manager-idm3/linking-two-inels-central-units-over-modbus-ip.md) |
| Modbus reads nothing at all               | A/B swapped, wrong baud, wrong slave address   | [32 §32.10](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)             |
| Modbus works with 2 devices, fails with 5 | Termination or topology                        | [32 §32.4](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| Temperature reads 215 instead of 21.5     | Scaling — set the multiplication factor        | [32 §32.10](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)             |
| Every Modbus value is one register out    | Register number vs offset (40001 vs 0x0000)    | [32 §32.5](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| Can I control a Carrier air conditioner   | Yes, via a CCN→Modbus translator               | [32 §32.8](/inels-bus/inels-design-manager-idm3/idm3-modbus-rtu-and-ip-integration.md)              |
| The external system can't see a device    | It isn't marked **Add to iNELS 3 export**      | [24 §24.2](/inels-bus/inels-design-manager-idm3/idm3-external-systems-mqtt-modbus-cloud.md)         |
| A phone app for the client                | Cloud                                          | [22 §22.3](/inels-bus/inels-design-manager-idm3/idm3-central-unit-configuration.md)                 |

## DALI

| The customer says                             | Answer                                        | Chapter                                                                         |
| --------------------------------------------- | --------------------------------------------- | ------------------------------------------------------------------------------- |
| How do I address DALI ballasts                | CU3-09M: Dali manager. RC3-610M: externally.  | [21 §21.1](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |
| Which CU do I need for DALI                   | **CU3-09M** — or an RC3-610M/DALI unit        | [21 §21.1](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |
| Dali manager doesn't see my ballasts          | The CU isn't a CU3-09M                        | [21 §21.1](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |
| RC3-610M DALI lights don't respond            | Ballasts must be addressed externally first   | [21 §21.6](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |
| DALI bus completely dead                      | DALI needs its own power supply               | [21 §21.1](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |
| All my DALI lights control the wrong fittings | Someone ran **New DALI** on a live system     | [21 §21.3](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |
| Which fitting has failed                      | **Lamp failure** in the Dali manager status   | [21 §21.5](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |
| Duplicate DALI address                        | Red exclamation mark — use **Delete address** | [21 §21.4](/inels-bus/inels-design-manager-idm3/idm3-dali-manager-reference.md) |

## Messaging

| The customer says                          | Answer                                 | Chapter                                                                               |
| ------------------------------------------ | -------------------------------------- | ------------------------------------------------------------------------------------- |
| SMS never arrives                          | The **GSM:** plug is red, not green    | [13 §13.4](/inels-bus/inels-design-manager-idm3/tutorial-alarms-and-sms-messaging.md) |
| Can it text me when something happens      | Yes — GSM3-01M required                | [13](/inels-bus/inels-design-manager-idm3/tutorial-alarms-and-sms-messaging.md)       |
| My text to the system does nothing lasting | Incoming SMS is a **one-second** pulse | [13 §13.4](/inels-bus/inels-design-manager-idm3/tutorial-alarms-and-sms-messaging.md) |
| Message got cut off                        | 32-character limit                     | [19 §19.6](/inels-bus/inels-design-manager-idm3/idm3-managers-reference.md)           |

## Software and versions

| The customer says                                     | Answer                                                                                            | Chapter                                                                           |
| ----------------------------------------------------- | ------------------------------------------------------------------------------------------------- | --------------------------------------------------------------------------------- |
| Where do I download iDM3                              | [Software Download](https://wiki.inels.com/inels-bus/inels-design-manager-idm3/software-download) | [3](/inels-bus/inels-design-manager-idm3/installing-idm3-and-first-run.md)        |
| Which central units are supported                     | CU3-08M / 09M / 10M; CU3-07M obsolete                                                             | [1 §1.2](/inels-bus/inels-design-manager-idm3/what-inels3-and-idm3-are.md)        |
| Is EST3 / EHT3 still available                        | Obsolete — use a GSB3 or similar                                                                  | [Appendix D](/inels-bus/inels-design-manager-idm3/idm3-supported-units.md)        |
| What's the difference between Short down and Short up | Down = press, up = release                                                                        | [2 §2.2](/inels-bus/inels-design-manager-idm3/how-programming-works-in-idm3.md)   |
| Why does it say "for CU3-07M"                         | Historical naming                                                                                 | [3 §3.2](/inels-bus/inels-design-manager-idm3/installing-idm3-and-first-run.md)   |
| My old project won't open properly                    | Needs conversion — **and a connection to the CU**                                                 | [28](/inels-bus/inels-design-manager-idm3/opening-older-idm3-projects.md)         |
| A unit isn't supported any more                       | **Unavailable units**                                                                             | [28 §28.4](/inels-bus/inels-design-manager-idm3/opening-older-idm3-projects.md)   |
| iDM3 won't start                                      | .NET Framework 4.8; check `Exception.excp`                                                        | [3 §3.7](/inels-bus/inels-design-manager-idm3/installing-idm3-and-first-run.md)   |
| Where are the log files                               | The install folder                                                                                | [30 §30.6](/inels-bus/inels-design-manager-idm3/troubleshooting-idm3.md)          |
| It's very slow                                        | Turn off the two animations                                                                       | [30 §30.6](/inels-bus/inels-design-manager-idm3/troubleshooting-idm3.md)          |
| I've run out of wires / bits                          | **Prefernces** shows the limits                                                                   | [27 §27.3](/inels-bus/inels-design-manager-idm3/idm3-settings-and-preferences.md) |

***

## Things that look like bugs but aren't

Worth checking before escalating — each is documented behaviour:

| Behaviour                                     | Why                                               |
| --------------------------------------------- | ------------------------------------------------- |
| Second press does nothing                     | `Digital switch ON` is not a toggle               |
| Impulse won't re-trigger                      | `Digital_Impulse_ON` ignores an output already on |
| Light climbs to full after dimming            | No `Analog stop changing level` on `Long up`      |
| Ramp finishes early                           | Ramp length is the 0→100% time                    |
| Group function names look raw                 | Untranslated in 3.5.3                             |
| `Alarm_Refeshed` is misspelled                | It is — in the software                           |
| Menu says "Prefernces"                        | It does                                           |
| **New unit** greyed out                       | Wrong item selected, or a limit reached           |
| Editing a macro doesn't change existing wires | Macros are copied, not linked                     |

***

**See also:** [Chapter 30 — Troubleshooting](/inels-bus/inels-design-manager-idm3/troubleshooting-idm3.md) · [Appendix E — Glossary](/inels-bus/inels-design-manager-idm3/idm3-glossary.md) · [index](/inels-bus/inels-design-manager-idm3/idm3-user-manual-contents.md)