Common questions — support index

Support index — a symptom or question, and the chapter that answers it.


This page exists to get you from a customer's words to the right chapter fast. It is phrased the way people actually ask, not the way the manual is organised.


"It doesn't work"

The customer says
Likely cause
Chapter

The button does nothing at all

Icon not assigned — yellow dot on the floor plan

I uploaded but nothing changed

Saved the file but never did Save to central unit

It worked before, now it doesn't

The CU is running a different project

Some devices are missing / disconnected

Addresses don't match the hardware

The relay clicks but the light stays off

The project is right — the fault is electrical

Nothing responds after a power cut

Non-volatile not set; no System start wire

Lights and switching

The customer says
Answer
Chapter

The button only turns the light on, never off

Digital switch ON isn't a toggle — use DIGITAL_SWITCH

I want a staircase light that switches itself off

Impulse function with an impulse time

Pressing again doesn't restart the timer

Digital_Impulse_ON ignores an output already on — use a timer

I want one button to do two things

Two actions on one wire — Short down and Long down

I want a delay before it switches off

Digital delay switch OFF

How do I switch everything off from one button

A group

Dimming

The customer says
Answer
Chapter

The light runs to 100% after I let go

Missing Analog stop changing level on Long up

Holding the button doesn't dim

Needs Analog increasing level on Long down

The dimmer forgets its brightness

Analog switch value only moves 0%↔100% — needs a system integer

My 10-second ramp only takes 2 seconds

Ramp length is the 0→100% time; partial changes are proportional

I want the light to fade, not jump

Analog set level w ramp

I want a specific brightness on one press

ANALOG_SET_LEVEL_25/50/75

Blinds and shutters

The customer says
Answer
Chapter

How do I control blinds

Digital impulse — short time tilts, long time runs full travel

The blind won't stop when I press again

Digital_Impulse_ON ignores an active output — add an explicit stop

The blind doesn't reach the end

Impulse time shorter than real travel time

The slats tilt too far

Reduce the tilt impulse time

Can blinds close at sunset

Astronomical module

Heating and cooling

The customer says
Answer
Chapter

Heating doesn't come on

Check Monitor → Heat/Cool areas first

The temperature is wrong

The time plan, or which plan the area uses

How do I set a heating schedule

Time plan, then Heat/Cool area

Heating and cooling run at the same time

Check the difference between…On

One room never heats

That room's Heating output

No room heats

The shared Heating supply

How do I protect against freezing

Antifreeze temperature on every area

What are Favorite1–4

The four preset temperatures

Holiday mode for heating

Holiday plan + a continuous program

Timers, counters, logic

The customer says
Answer
Chapter

Corridor light should restart on movement

A timer — Timer start restarts a running timer

I want to count something

A counter

How do I remember a state

A system bit, non volatile

Holiday mode is lost after a reboot

non volatile wasn't ticked

Only do this if it's dark / cold / off

A condition

What do system bits and integers do

Storage the whole project can read and write

Schedules and time

The customer says
Answer
Chapter

Do something at a set time

A Periodical program

On for part of the week

A Two-state program

Between two dates

A Continuous program

I can't save my program

No day or month ticked

Sunset switching is an hour out

The CU's Time zone

Lights on at dusk all year

Astronomical module with a sunset offset

Connection and upload

The customer says
Answer
Chapter

I can't connect to the central unit

Ping test first

It says BadPassword

Wrong CU password

It says UpdateRequired

CU firmware too old

Compile error

Click the button and read it

I lost the project file

Load from central unit

How do I change the CU's IP address

CU configuration

Groups, scenes and reuse

The customer says
Answer
Chapter

A light won't join my group

Wrong group type — relays and dimmers can't share one

How do I build a scene

Separate wires with different levels, not a group

The group function names look wrong

Untranslated in 3.5.3 — GroupDigital_SwitchOn is normal

I keep building the same thing

Macros, or function blocks

My macro didn't apply

Its Type doesn't match the actor type

Editing the macro changed nothing

Macros are copied into wires, not linked

A function block does nothing

Inputs/outputs not plugged in, or Connect not pressed

A colleague can't open my project properly

Function block templates live outside the .elp

Hotel installations

The customer says
Answer
Chapter

Rooms don't show up in iNELS Harmony

No Hotel-Room object — Harmony discovers rooms from it

What is the Hotel-Room object for

One object per guest room: status, climate, scenes

Where do I enter the room number

Room-Id on the Hotel-Room unit — not the Address

Guest can set a temperature but nothing happens

Heat/Cool area outputs never wired to hardware

How does the PMS read a room

One MQTT topic pair per room

DND light doesn't match the button

Drive the backlight from the DND datapoint

Empty rooms stay warm

Wire Occupancy off → setback

Integration

The customer says
Answer
Chapter

Can I use it with Home Assistant

MQTT

MQTT isn't working

Needs CU firmware 02.97.02 or later

Can I read an energy meter

Modbus master

Can a BMS read the installation

Modbus slave

Does it do Modbus RTU or just TCP

Both — but RTU needs a CU3-10M

Internal-Modbus-Master isn't in the list

The CU isn't a CU3-10M

RTU meter, but the site has a CU3-08M

Gateway, CU swap, or GRT3-100 master

Which CU do I need for Modbus

IP: any. RTU: CU3-10M only.

Can two central units talk to each other

Yes — Modbus IP

Button on one CU, light on another

Link them over Modbus IP

CU link worked, then stopped

The slave CU's IP changed — DHCP

Value moves on one CU, not the other

Register address, data type or scaling differs

How do I share a temperature between CUs

One register, Multiplication 10x both sides

Modbus reads nothing at all

A/B swapped, wrong baud, wrong slave address

Modbus works with 2 devices, fails with 5

Termination or topology

Temperature reads 215 instead of 21.5

Scaling — set the multiplication factor

Every Modbus value is one register out

Register number vs offset (40001 vs 0x0000)

Can I control a Carrier air conditioner

Yes, via a CCN→Modbus translator

The external system can't see a device

It isn't marked Add to iNELS 3 export

A phone app for the client

Cloud

DALI

The customer says
Answer
Chapter

How do I address DALI ballasts

CU3-09M: Dali manager. RC3-610M: externally.

Which CU do I need for DALI

CU3-09M — or an RC3-610M/DALI unit

Dali manager doesn't see my ballasts

The CU isn't a CU3-09M

RC3-610M DALI lights don't respond

Ballasts must be addressed externally first

DALI bus completely dead

DALI needs its own power supply

All my DALI lights control the wrong fittings

Someone ran New DALI on a live system

Which fitting has failed

Lamp failure in the Dali manager status

Duplicate DALI address

Red exclamation mark — use Delete address

Messaging

The customer says
Answer
Chapter

SMS never arrives

The GSM: plug is red, not green

Can it text me when something happens

Yes — GSM3-01M required

My text to the system does nothing lasting

Incoming SMS is a one-second pulse

Message got cut off

32-character limit

Software and versions

The customer says
Answer
Chapter

Where do I download iDM3

Which central units are supported

CU3-08M / 09M / 10M; CU3-07M obsolete

Is EST3 / EHT3 still available

Obsolete — use a GSB3 or similar

What's the difference between Short down and Short up

Down = press, up = release

Why does it say "for CU3-07M"

Historical naming

My old project won't open properly

Needs conversion — and a connection to the CU

A unit isn't supported any more

Unavailable units

iDM3 won't start

.NET Framework 4.8; check Exception.excp

Where are the log files

The install folder

It's very slow

Turn off the two animations

I've run out of wires / bits

Prefernces shows the limits


Things that look like bugs but aren't

Worth checking before escalating — each is documented behaviour:

Behaviour
Why

Second press does nothing

Digital switch ON is not a toggle

Impulse won't re-trigger

Digital_Impulse_ON ignores an output already on

Light climbs to full after dimming

No Analog stop changing level on Long up

Ramp finishes early

Ramp length is the 0→100% time

Group function names look raw

Untranslated in 3.5.3

Alarm_Refeshed is misspelled

It is — in the software

Menu says "Prefernces"

It does

New unit greyed out

Wrong item selected, or a limit reached

Editing a macro doesn't change existing wires

Macros are copied, not linked


See also: Chapter 30 — Troubleshooting · Appendix E — Glossary · index